2-position 3-way solenoid pilot valve for on-off service
I have some question about the on-off valve (please see attachment)
N1.What is the Limit switches (in this case) used for?( Ex. permissive or trip initiators for interlock)
N2. Why does this limit switch on the on-off valve not provide any alarm in the control room?
(At least I can't see any in the attachment drawing)
N3. Our (process engineers) are ask for deciding these pneumatic hand switch (*HS A/B in the attached drawing) remote open/close from DCS is necessary or not.
However, I understand it has to be depending on the process people's apprehension for the process.
Anyone could kindly help me out, and give me suggestion that how to find any implication about this HS requiring or not from the process interlock description or any other document.
The P&ID depicts position switch contacts wired to the DCS. The I
could include some interlock logic in addition to the status
display. This example does not appear to include automatic valve
actuation, only operator initiated remote activation.
BTW, I
prefer the term position switch for contacts that provide open or closed
position status. The term limit switch is often used on eletrick motor operated valves describing contacts that stop the motor when the valve is at full open or travel.
The
open or closed status of a valve is not necessarily and alarm
situation. This appears to be operator initiated activity to open or
close the valve. Hwoever the open status could be used as an interlock
to permit starting a pump, etc.
N3. Our (process engineers) are
ask for deciding these pneumatic hand switch (*HS A/B in the attached
drawing) remote open/close from DCS is necessary or not.
The
operating philosophy or project engineering standards might define when
valves should be remotely operated. However the P&ID reflects the
automated valve actuator. With the hardware
provided it makes sense to permit the operator to open and close
remotely. Often the valve pneumatic components include a selector to
permit opening or closing at the valve/ball valve. This scheme suggests a double
acting valve, no spring or failure position. A volume bottle could
provide stored energy to operate when the air supply fails. The
de-energized direction on the solenoid valve suggests that this is a
spring operated valve. The failure position of the valve is not
shown. If a blowdown valve different clients have different
requirements. Fail closed is normal for an isolation or shutdown
valve. If it is an emergency shutdown valve a selector could be for
automatic or close instead of open or close. This could prevent
isolating the automatic control.
MORE NEWS