Probelm with MOV passing
I have a problem with MOV motor operated valve paaing through. when I looked at the MOV data sheet, it was not speified that the valve as Tight Seal Closed but it is referred the seat leakage rate to API 598. So, i realized that the passing from the seat. Can any body help me to find a way to stop the passing?
Play with the actuator limit stops to assure that the valve is fully
closed. This is easy with the valve out of the line but can be adjusted
slightly with some trial and error inline.
Pump the lubricators with grease.
Remove and send the valve to a shop.
As a non-english native I assume MOV stands for motor operated valve, and that the motor is an electrical actuator.
I
fthis is correct I will support JLSeagull and add that a first class
actuator will have both torque and limit switches for open and closed
included.
In this case it is important that the closing (and
opening) is stopped by the limit switches at a point where the valve is
thight enough.
The torque switch for closing should be
set/adjusted higher than the necessary closing torque, but not used to
stop the valve in closed position, or stop the valve before properly
closed. (The limit switch will give closed position, and should be
accordingly adjusted, as mentioned above).
If valve is not thight
enough after adjustment: seat or seat-sealing is damaged or you have a
non-satisfactorily valve in general.