Water Main Leakage Test - Calculate theoretically?
I recently witnessed a pressure test followed by the leakage
test. Pressure dropped from 161psi to 159psi for 5,710 ft of 8-inch DI
pipe. Is there a way for me to verify the leakage (7.5 gal)
theoretically?
I'm suspicious of the leakage number because
they pulled the suction line out of the water tank used to pump the line
up....and I suspect air got in the suction line and messed with the
test. Thanks for any help you can provide!
Additionally be suspicious if the contractor sees an instantaneous jump on the gauge and sucked air as you describe as the system can become air locked and is pointless after that. Contractors try everything from a "secret" buried valve or curbstop to pass if a line has become troublesome. Pay careful attention to the setup and make sure you understand the location of every valve, hydrant, and blowoff.
I fear a reader to this thread might come out of it with some
misunderstanding of the specific test it appears was performed, as well
as the complexity in general of hydrostatic testing issues. To begin
with my reading of the formula as well as tables of C600 tells me that
when make-up water must be pumped back into an 8" ductile iron pipeline
5,710 feet long tested at say 160 psi, the ALLOWABLE "testing allowance"
for a two hour test per this standard should not exceed:
L=(2
hrs) (5,710)(8)160^.5/148,000 or 7.81 gallons. [It appears the
contractor in this case for whatever reason pumped only 7.5 gallons back
in, that would appear to be a "pass" at least per the AWWA standard .]
With
all due respect also to some of the verbiage and terminology in
references in this thread, as well as in some of the responses, I feel
compelled to make the following additional comments related to the
further, original question in general of "calculating leakage". In my
opinion, while it is possible to do all manner of calculations e.g. with
"bulk modulus of compressibility" of water and elastic stretching of
pipes etc. it is generally not really practical to "calculate leakage"
in buried pipeline tests (except maybe in some very HIGHLY controlled
test conditions of vessels and limited pipelines). This is due to the
following realities, some that may really be common to installation of
pipelines of all materials:
1. Despite best intentions/design,
most rigorous or expensive installation/construction, and inspections
etc., pipelines are not necessarily laid precisely with regard to either
the horizontal or e.g. vertical lines on plans etc.
2. Similar to
the realities/imperfections of "1.", air valves and/or other air release
mechanisms etc. are not necessarily always installed precisely at the
top or apex of all local, vertical crests that may happen by design, or
inadvertently in the installation of pipelines.
3. Due to the combination of "1." and "2.", some air inevitably becomes trapped in pipelines.
4. As
most venerable standards and specifications also require that pipelines
be filled, e.g. in preparation for hydrostatic testing "slowly"
[defined in some as at velocities <1 fps (0.3mps)], it is also a
reality (at least when high velocity flushing is not accomplished prior
to hydrostatic testing) that that any unintentionally trapped and
unvented air will simply not be removed (or "scavenged by sufficiently
high flow velocity) at the time the (in effect combination air and water
containing) pipeline is pressurized in hydrostatic testing.
5. While
trapped air may or admittedly may not cause any sort of noticeable
problems in subsequent hydrostatic text results, it is well known that
it CAN wreak literal havoc in others. In other words, pipelines that
contain trapped air can appear in various fashions to sometimes fail
hydrostatic testing criteria (incidentally either raising or falling in
pressure, or requiring excessive make-up water!), even though they
really have no leakage!
6. For this reason, it is also stated in
many long-standing specifications that the installer should remove most
or all air (a requirement that appears, at least in many circumstances,
sometimes easier said than done and some incongruous with the realities
of 1-4!)
7. Unlike water, that as you note is relatively
"incompressible", air is instead highly compressible, and air is also
highly volume or pressure (if contained as in a closed hydrostatic test)
responsive to changes in temperature in accordance with "Boyle's",
"Charles'" and "Gay Lussacs'" et al laws/principles. Thus if (indeed
probably instead "when", in the case of much testing that is of rather
long duration) there are any temperature changes this will be
accompanied by inevitable changes in pressure etc. and/or
disproportionate requirements for make-up water etc., that do not have
anything to do with "leakage".
8. It may be tempting to just assume
that pressurized air is just like pressurized water (the old "pressure
is pressure" argument), and therefore will not meaningful affect test
results. However, this argument appears to neglect yet another
phenomena associated with air/water mixes, that being that when there is
no separating membrane air is also somewhat free also go into and out
of "solution", and this in turn is probably also influenced by various
drivers/variables of pressure and changing temperature etc. (not to
mention the locations of at least any large columns of air e.g. from the
pressurizing end etc.). While much at least surface source water is
already "saturated" with air, this may not be true of all filling water
sources, and also other conditions. In this regard I saw a writing many
years ago (I think from a manufacturer of air valves), "A typical 1-mi
(2-km) long pipeline of any diameter that has been supposedly vented of
air will, in most instances, still contain enough dissolved air to
completely fill over 100 ft (30 m) of the pipe." Likewise, some water
can soak into cement mortar linings of some types of pipe, also over
time/pressure.
9. Lastly, it is also possible that there can be
slight movement, settlement, or some extension of pipelines due to
installation and/or Bourdon effects etc., again that has nothing
necessarily to do with leakage but that would change the test volume and
manifest itself in at least some loss of pressure during a long-term
test.
I think many of these practical realities were not lost on
at least the formulators of venerable standards that have existed for
decades, e.g. ANSI/AWWA C600 for the installation and testing of iron
pipelines. In this regard, if after more than 2 hours a particular
closed off small diameter pipeline still holds basically a 160 psi level
of pressure, while only losing a pound or two of water pressure, I
suspect many Owners or installers of pipelines of many materials would
probably be pretty happy with such an apparently tight line. As psnyder
notes/quotes above, the C600 standard indeed states, "Testing allowance
shall be defined as the maximum quantity of makeup water that is added
into a pipeline undergoing hydrostatic pressure testing... IN ORDER TO
MAINTAIN PRESSURE within